RS485 Communication

Official Installation Manual (archived)

Hardware

The two EM24 Sensors are connected with the PowerRouter via RS485 bus. They are connected via standard CAT-cables. The jack is at the right side of the PowerRouter and labeled CAN. Be careful, it's the one at the backside, the jack at the front has some LEDs and is for the network communication!

As mentioned in the Installation Manual the Sensors are connected as follow:

     [cable] -> [EM24]
 white/green -> 41 (A-)
       green -> 42 (B+)
white/orange -> 43 (GND)

The cable seems to be wired by T568B thus it appears that the following pinout is used:

[RJ45] -> [RS485]
     3 -> A-
     6 -> B+
     1 -> GND

But as explained on wikipedia the data lines of the transceiver SP3485 is swapped.

[RJ45] -> [RS485] -> [SP3485]
     3 ->    A-   -> B (Inverting)
     6 ->    B+   -> A (Non-Inverting)
     1 ->   GND   -> GND

Serial Port Settings

  • baud: 9600
  • stop bits: one
  • parity: none

Protocol

Sample communication

01 03 00 0c 00 0a 05 ce
01 03 14 01 c9 00 00 02 33 00 00 04 d5 00 00 01 42 00 00 04 85 00 00 74 9f
01 03 00 16 00 08 a5 c8
01 03 10 0a 37 00 00 04 0e 00 00 05 07 00 00 0a c4 00 00 24 15
02 03 00 46 00 06 24 2e
02 03 0c 00 00 00 00 00 00 00 00 c9 ad 00 03 3e 0d
01 03 00 0c 00 0a 05 ce
01 03 14 01 c9 00 00 02 33 00 00 04 e1 00 00 01 42 00 00 04 85 00 00 9e af
01 03 00 16 00 08 a5 c8
01 03 10 0a 57 00 00 03 f5 00 00 05 09 00 00 0a e2 00 00 99 da
01 03 00 00 00 06 c5 c8
01 03 0c 08 e1 00 00 08 f2 00 00 08 b7 00 00 41 bf
01 03 00 0c 00 0a 05 ce 
01 03 14 01 be 00 00 02 3b 00 00 04 df 00 00 01 12 00 00 04 85 00 00 e2 fb
01 03 00 16 00 08 a5 c8
01 03 10 0a 4d 00 00 03 f5 00 00 05 1b 00 00 0a de 00 00 f1 dc 
01 03 00 46 00 06 24 1d
01 03 0c 2e 7b 00 01 bb 15 00 00 a3 0f 00 00 65 2c
01 03 00 0c 00 0a 05 ce
01 03 14 01 c1 00 00 02 31 00 00 04 f5 00 00 00 f5 00 00 04 85 00 00 b9 f8
01 03 00 16 00 08 a5 c8
01 03 10 0a 76 00 00 03 fd 00 00 05 04 00 00 0b 0f 00 00 1f ab
02 03 00 0c 00 0a 05 fd
02 03 14 00 00 00 00 00 29 00 00 00 42 00 00 00 00 00 00 ff e1 ff ff 21 77
01 03 00 0c 00 0a 05 ce
01 03 14 01 bf 00 00 02 35 00 00 04 f5 00 00 01 04 00 00 04 8c 00 00 7c d8
01 03 00 16 00 08 a5 c8
01 03 10 0a 43 00 00 03 f9 00 00 05 0d 00 00 0a cd 00 00 c6 8c
02 03 00 16 00 08 a5 fb
02 03 10 ff f9 ff ff 00 00 00 00 00 5d 00 00 00 93 00 00 4f 06
01 03 00 0c 00 0a 05 ce
01 03 14 01 db 00 00 02 35 00 00 04 d8 00 00 00 e9 00 00 04 80 00 00 bf 4d
01 03 00 16 00 08 a5 c8
01 03 10 0a 43 00 00 04 39 00 00 05 0d 00 00 0a cd 00 00 cf 44
02 03 00 46 00 06 24 2e
02 03 0c 00 00 00 00 00 00 00 00 c9 ad 00 03 3e 0d
01 03 00 0c 00 0a 05 ce
01 03 14 01 c4 00 00 02 35 00 00 04 d8 00 00 01 4b 00 00 04 80 00 00 6e 9d
01 03 00 16 00 08 a5 c8
01 03 10 0a 44 00 00 04 00 00 00 05 0d 00 00 0a cd 00 00 59 da

The hexdump above shows the requests of the PowerRouter and the response of the EM24-DIN. The request is structured as following:

01 03 00 16 00 08 a5 c8
                  ^^^^^ crc (bytes are swapped!)
            ^^^^^------ quantity of parameters to read
      ^^^^^------------ start address
   ^^------------------ function code: 03: read holding registers
^^--------------------- device address

The response:

01 03 10 0a 37 00 00 04 0e 00 00 05 07 00 00 0a c4 00 00 24 15
                                                         ^^^^^ crc (bytes are swapped!)
         ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^------ data
      ^^------------------------------------------------------ bytes transfered
   ^^--------------------------------------------------------- function code
^^------------------------------------------------------------ device address

The communication protocol and data can be decoded with the help of the official EM24-DIN Communication Protocol Manual (archived) of the energy meter.